Features

  • It is available to attach an alarm indicating fuse(microswitch can be installed).
  • Also compliant to 400V DC (350GH)
  • It is available to attach an alarm indicating fuse(microswitch can be installed).

Rating

250GH

Rated voltage and blocking capacity
AC250V-100kA
DC250V(L/R10ms)-100kA
Minimum block-off current
AC/DC250V - 5 times the rated amperage
Maximum arc voltage
550V

350GH

Rated voltage and blocking capacity
AC350V-100kA
DC400V(L/R2ms)-10kA
Minimum block-off current
AC350V/DC400V - 5 times the rated amperage
Maximum arc voltage
800V

250GH

350GH

UL standard approved rating

250GH(cUL not approved)

Rated voltage and blocking capacity
When applying the standard to UL standard approved items, use the fuse in the following rating.

AC250V-100kA DC250V(L/R10ms)-100kA

350GH

Rated voltage and blocking capacity
When applying the standard to UL standard approved items, use the fuse in the following rating.

AC380V-10kA
DC400V(L/R2ms)-10kA

CCC standard approved rating

350GH

Rated voltage and blocking capacity
When applying the standard to CCC standard approved items, use the fuse in the following rating.

AC350V-50kA DC250V(L/R10ms)-50kA

Rated Voltage

250V / 350V

Rated Current

16~800A

Cylinder Size(Estimated)

φ17×25~

Installation Method

Screwed

RoHS Order

Standard Approved

cUL CCC

Specifications

Product Image

Dimensions

<FIg1>

<FIg1>

<Fig2>

<Fig2>

※HT4017 (option)

※HT4017 (option)

※HT5723 (option)

※HT5723 (option)

Fusing Characteristics

350GH

350GH

250GH

250GH

Current-Limiting Characteristics

350GH

350GH

250GH

250GH

Temperature Rise

350GH

350GH

250GH

250GH

Power Loss

350GH

350GH

250GH

250GH

Shutdown I²t Against Working AC Voltage

350GH

350GH

250GH

250GH

Application to Direct-Current Circuit

350GH

350GH

250GH

250GH