Products
250GH/350GH
Back to Products
Features
- It is available to attach an alarm indicating fuse(microswitch can be installed).
- Also compliant to 400V DC (350GH)
- It is available to attach an alarm indicating fuse(microswitch can be installed).
Rating
250GH
- Rated voltage and blocking capacity
- AC250V-100kA
DC250V(L/R10ms)-100kA - Minimum block-off current
- AC/DC250V - 5 times the rated amperage
- Maximum arc voltage
- 550V
350GH
- Rated voltage and blocking capacity
- AC350V-100kA
DC400V(L/R2ms)-10kA - Minimum block-off current
- AC350V/DC400V - 5 times the rated amperage
- Maximum arc voltage
- 800V

250GH

350GH
UL standard approved rating
250GH(cUL not approved)
- Rated voltage and blocking capacity
- When applying the standard to UL standard approved items, use the fuse in the following rating.
AC250V-100kA DC250V(L/R10ms)-100kA
350GH
- Rated voltage and blocking capacity
- When applying the standard to UL standard approved items, use the fuse in the following rating.
AC380V-10kA
DC400V(L/R2ms)-10kA
CCC standard approved rating
350GH
- Rated voltage and blocking capacity
- When applying the standard to CCC standard approved items, use the fuse in the following rating.
AC350V-50kA DC250V(L/R10ms)-50kA
Rated Voltage
250V / 350V
Rated Current
16~800A
Cylinder Size(Estimated)
φ17×25~
Installation Method
Screwed
RoHS Order
◯
Standard Approved
Specifications

Dimensions
<FIg1>

<Fig2>

※HT4017 (option)

※HT5723 (option)

Fusing Characteristics
350GH

250GH

Current-Limiting Characteristics
350GH

250GH

Temperature Rise
350GH

250GH

Power Loss
350GH

250GH

Shutdown I²t Against Working AC Voltage
350GH

250GH

Application to Direct-Current Circuit
350GH

250GH